Emerson Vertiv Online UPS

Reliable Power, Uninterrupted Performance!

True Online Double Conversion UPS with optional built - in galvonic isolation & with extended runtime capabilities

Liebert GXT MT+ Series systems is true double conversion online UPS systems designed to provide with a capacity of 6/10/20 kVA. Liebert GXT MT+ units feature total isolation of the load from the mains – isolating input and output sections, and making the systems ideal for Data Networks / Small Data Centers/VOIP Applications application. The units support hot standby configuration, making them suited for critical applications like banks.

Technical Specification

MODEL GXT MTX+ 06 KVA GXT MT+ 06 KVA GXT MT+ 10 KVA GMT MT+ 10KVA GMT MT+ 20KVA
PHASE 1 phase in 1 phase in / 1 phase out 1 phase in 3 phase in / 1 phase out 3 phase in / 1 phase out
CAPACITY 6000 VA / 4800 Watt 6000 VA / 4800 Watt 10000 VA / 8000 10000 VA / 9000 W 20000 VA / 18000 W
INPUT Characteristics
Nominal Voltage 230 Vac (1 Ph + N) 3 x 400 VAC (3Ph+N)
Voltage Range 160 Vac–300 Vac (1-phase) @ 100% load 305–478 VAC (3-phase) @ 100% load
Frequency Range 46–54 Hz or 56–64 Hz
Power Factor ≥ 0.99 @ 100% load
THDi < 6% @ 100% load
OUTPUT Characteristics
Output Voltage 208 / 220 / 230 / 240 VAC
AC Voltage Regulation (Batt. Mode) ± 1%
Frequency Range (Synchronized) 46–54 Hz or 56–64 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio 3:1 (max)
Harmonic Distortion ≤ 2% THD (Linear Load)   |   ≤ 5% THD (Non-linear Load)
Transfer Time AC Mode to Batt. Mode – Zero
Waveform (Batt. Mode) Pure Sinewave
AC Mode Efficiency >84% 91% >92% >92%
ECO Mode Efficiency 97%
BATTERY Characteristics
Battery Type SMF SMF or Tubular
Numbers 16–20*** (adjustable) 18–20*** (adjustable)
Charging Current (max.) 6 Amps settable to 1/2/3/4/5/6 Amps 12A settable to 2/4/6/8/10/12 Amps
Charging Voltage 273 VDC ± 1% (Based on 20pcs batteries)
INDICATORS
LCD Panel UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions
ALARM
Battery Mode Sounding every 4 seconds
Low Battery Sounding every second
Overload Sounding twice every second
Fault Continuously sounding
PHYSICAL
Dimension, D × W × H (mm) 369 × 190 × 630 369 × 190 × 318 442 × 190 × 318 592 × 250 × 576 >592 × 250 × 826
Net Weight (kgs) 72 21 28 45
ENVIRONMENT
Operation Humidity 0–95 % RH @ 0–40°C (non-condensing)
Noise Level < 65 dB @ 1 meter < 55 dB @ 1 meter < 58 dB @ 1 Meter < 60 dB @ 1 Meter
MANAGEMENT
Smart RS-232/USB Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux, Unix, and MAC
Optional SNMP Power management from SNMP manager and web browser